1. Start:
(1) the following 11 kw pumps allow direct start, 13 kw or more pumps should be equipped with step-down starting cabinet, to protect the safe operation of electric pump.
(2) in order to avoid the electric pump rotor moment and reduce the starting load, electric pump start-up time should be the outlet valve stroke off to 3/4. (leave a quarter of the air gap. In order to put gas) to start after the water slowly open, to pump under control in the appropriate position.
(3) started running after the start, should strengthen the supervision and the observed water level change, ensure pumps within the scope of the condition of operation, can be put into operation after pumps running smoothly.
(4) pumps in operation for the first time after five hours, stop quickly measuring thermal insulation resistance, its value is not less than 0.5 M Ω, can continue to use.
2. Stop the pump:
Before electric pump stop, to prevent the backflow of water, at the same time of cut off the power to close the valve, restart time every 20 minutes.
3. The operation and maintenance:
(1) pumps should be to work in the design point, the axial force is moderate, pump efficiency is highest, the most economical and reliable. (2) pumps every work 8 hours to full check, each instrument for change, whether the circuit nodes fever, voice is normal. Whether the normal working current is greater than the motor nameplate rating.
4. One of the following circumstances, should immediately stop the pump:
(1) the working current of the pump suddenly above the motor rated current
(2) the water yield is not normal, gap water, sediment concentration increased
(3) the motor insulation resistance is lower than 0.5 ohms
(4) has obvious noise vibration of unit
(5) power grid voltage is not enough, less than 5% of the rated voltage
(6) the fuse burned a phase
(7) delivery road damage
5. Matters needing attention in operation and maintenance:
(1) check that the current voltage and discharge pressure every day, every 2 weeks testing dynamic water level, and make records.
(2) every four weeks to check the insulation resistance of motor and make records.
(3) use of start times to reduce as far as possible.
(4) pumps if well under discontinuous after use, should boot up once a week, and run the 5-10 minutes, to prevent pumps for corrosion can't start.
6. Electric pump storage and handling:
Store to put a net electric pump motor cavity effusion, dry surface, shaft coupling head to besmear antirust oil, erected in place. (in order to prevent the rotor deformation) in a dry, no chemical corrosive articles, normal temperature, winter storage of not less than 3 ℃ temperature.